* 600V CAT IV/1000V CAT III rated for use at the service entrance and downstream
* Power instrument directly from the measured circuit
* Automatically capture and log voltage, current, power, power factor, energy and associated values
Voltage |
||
Range |
1000 V |
|
Maximum Resolution |
0.1 V |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.2% + 0.01%) |
|
i17xx-Flex 1500 12" |
||
Range |
150 A 1500 A |
|
Maximum Resolution |
0.1 A 1 A |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(1% + 0.02%) ±(1% + 0.02%) |
|
i17xx-flex 3000 24" |
||
Range |
300 A 3000 A |
|
Maximum Resolution |
1 A 10 A |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(1% + 0.03%) ±(1% + 0.03%) |
|
i17xx-flex 6000 36" |
||
Range |
600 A 6000 A |
|
Maximum Resolution |
1 A 10 A |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(.51% + 0.03%) ±(1.5% + 0.03%) |
|
i40s-EL Clamp |
||
Range |
4 A 40 A |
|
Maximum Resolution |
1 mA 10 mA |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.7% + 0.02%) ±(0.7% + 0.02%) |
|
Frequency |
||
Range |
42.5 to 69 Hz |
|
Maximum Resolution |
0.01 Hz |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.1%) |
|
Aux Input |
||
Range |
±10 V DC |
|
Maximum Resolution |
0.1 mV |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.2% + 0.02%) |
|
Voltage Min/Max |
||
Range |
1000 V |
|
Maximum Resolution |
0.1 V |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(1% + 0.1%) |
|
Current Min/Max |
||
Range |
Defined by accessory |
|
Maximum Resolution |
Defined by accessory |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(5% + 0.2%) |
|
THD on Voltage |
||
Range |
1000% |
|
Maximum Resolution |
0.1% |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±0.5 |
|
THD on Current |
||
Range |
1000% |
|
Maximum Resolution |
0.1% |
|
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±0.5 |
|
Active Power P Active Energy Ea |
||
Influence Quantity |
PF ≥0.99 |
|
Apparent Power S Active Energy Eap |
||
Influence Quantity |
0 ≤PF ≤1 |
|
Reactive Power Q Reactive Energy Er |
||
Influence Quantity |
0 ≤PF ≤1 |
|
Additional Uncertainty in % of Range |
||
Influence Quantity |
VP-N <250 V |
|
Power Supply |
||
Voltage Range |
100 to 500 V using safety plug input when powering from the measurement circuit 100 to 240 V using standard power cord (IEC 60320 C7) |
|
Power Consumption |
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
|
Efficiency |
>68.2% (in accordance with energy efficiency regulations) |
|
Maximum No-Load Consumption |
<0.3 W only when powered using IEC 60320 input |
|
Mains Power Frequency |
50/60 Hz ± 15% |
|
Battery |
Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
|
On-Battery Runtime |
Four hours in standard operating mode, up to 5.5 hours in power saving mode |
|
Charging Time |
<6 hours |
|
Data Acquisition |
||
Resolution |
16-bit synchronous sampling |
|
Sampling Frequency |
10.24 kHz at 50/60 Hz, synchronized to mains frequency |
|
Input Signal Frequency |
50/60 Hz (42.5 to 69 Hz) |
|
Circuit Types |
1-ϕ, 1-ϕ IT, split phase, 3-ϕ delta, 3-ϕ wye, 3-ϕ wye IT, 3-ϕ wye balanced, 3-ϕ Aron/Blondel (2-element delta), 3-ϕ delta open leg, currents only (load studies) |
|
Data Storage |
Internal flash memory (not user replaceable) |
|
Memory Size |
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events |
|
Basic Interval |
||
Measured Parameters |
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
|
Averaging Interval |
User selectable: 1, 5, 10, 30 sec, 1, 5, 10, 15, 30 min |
|
Averaging Time Min/Max Values |
Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200 ms |
|
Demand Interval (Energy Meter Mode) |
||
Measured Parameters |
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
|
Interval |
User selectable: 5, 10, 15, 20, 30 min, off |
|
Interfaces |
||
USB-A |
File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
|
WiFi |
File transfer and remote control via direct connection or WiFi infrastructure |
|
Bluetooth |
Read auxiliary measurement data from Fluke Connect® 3000 series modules |
|
USB-Mini |
Data download device to PC |
|
Voltage Inputs |
||
Number of Inputs |
4 (3 phases and neutral) |
|
Maximum Input Voltage |
1000 V RMS, CF 1.7 |
|
Input Impedance |
10 MΩ |
|
Bandwidth |
42.5 Hz to 3.5 kHz |
|
Scaling |
1:1 and variable |
|
Measurement Category |
1000 V CAT III/600 V CAT IV |
|
Current Inputs |
||
Number of Inputs |
3, mode selected automatically for attached sensor |
|
Input Voltage |
Clamp input: 500/50 mV rms; CF 2.8 |
|
Rogowski Coil Input |
150/15 mV rms at 50 Hz 180/18 mV rms at 60 Hz CF 4 All at nominal probe range |
|
Range |
1 to 150 A, 10 to 1500 A with thin flexible current probe i17XX-flex1500 12" 3 to 300 A, 30 to 3000 A with thin flexible current probe i17XX-flex3000 24" 6 to 600 A, 60 to 6000 A with thin flexible current probe i17XX-flex6000 36" 40 mA to 4 A, 0.4 to 40 A with 40 A clamp i40s-EL |
|
Bandwidth |
42.5 Hz to 3.5 kHz |
|
Scaling |
1:1 and variable |
|
Auxiliary Inputs |
||
Number of Inputs |
2 |
|
Input Range |
0 to ±10 V DC, 1 reading/s |
|
Scale Factor |
Format: mx + b (gain and offset) user configurable |
|
Displayed Units |
User configurable (7 characters, for example, °C, psi, or m/s) |
|
Wireless Connection |
||
Number of Inputs |
2 |
|
Supported Modules |
Fluke Connect® 3000 series |
|
Acquisition |
1 reading/s |
|
Environmental Specifications |
||
Operating Temperature |
14 to 122°F (-10 to 50°C) |
|
Storage Temperature |
−4 to 140°F (-20 to 60°C) With battery: −4 to 122°F (-20 to 50°C) |
|
Operating Humidity |
50 to 86°F (10 to 30°C) max. 95% RH 86 to 104°F (30 to 40°C) max. 75% RH 104 to 122°F (40 to 50°C) max. 45% RH |
|
Operating Altitude |
6561.7' (2000 m) up to 13,123.4' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV |
|
Storage Altitude |
39,370.1' (12,000 m) |
|
Enclosure |
IP50 in accordance with EN60529 |
|
Vibration |
MIL-T-28800E, Type 3, Class III, Style B |
|
Safety |
IEC 61010-1 IEC Mains Input: Overvoltage Category II, Pollution Degree 2 Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 IEC 61010-2-031: CAT IV 600 V/CAT III 1000 V |
|
Electromagnetic Compatibility (EMC) |
EN 61326-1: Industrial CISPR 11: Group 1, Class A Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
|
Temperature Coefficient |
0.1 x accuracy specification/°C |
|
General Specifications |
||
Color LCD Display |
4.3" (109.2 mm) active matrix TFT, 480 x 272 pixels, resistive touch panel |
|
Dimensions |
Instrument: 7.8 x 6.6 x 2.2" (19.8 x 16.7 x 5.5 cm) Power supply: 5.1 x 5.1 x 1.8" (13 x 13 x 4.5 cm) |
|
Weight |
Instrument: 2.5 lbs (1.1 kg) Power supply: 0.9 lb (400 g) |